GSK218MC Servo Alarm 0450

GSK218MC User:
He is currently presenting this alarm in the GSK218MC control that you sold us last year.
SERVO ALARM 0450
The alarm is displayed randomly, even when the machine is stopped or waiting. The electrical conditions were checked and the communication cables (green wires) are well connected, the LEDs on the controllers are ok. The voltage on the controllers is ok.
Could you suggest me some procedure to solve the problem? any particular parameter?
 
CNCmakers Support:
The two long GSK-LINK cables (normally 6 meters, from GSK218MC to GE2000T driber) must be poor contact, need to change these two cables.

—[Close]— —[ Back]— —[ Print]—